New Ultraflo U1000MKII-HM Clamp-on Heat Meter/Energy Meter. The New U1000MKII-HM is a “Best Value” Clamp-on, Ultrasonic heat meter alternative to traditional inline energy meters, for energy management and billing applications in domestic and commercial, district or shared heating or cooling systems. Offering significant installation cost and dry maintenance benefits over traditional inline products.
The U1000MKII-FM is an ultrasonic permanent/fixed clamp-on flow metering solution for measuring flow rate and total flow with a volume pulse output and optional Modbus or 4-20mA flow proportional output, which can be used as a stand-alone meter or as part of an integral management system.
Simple to install. Compact, rugged and reliable, the U1000MKII-FM has been designed to provide sustained performance in industrial environments.
SPECIFICATION:
- Measurement Technique: Ultrasonic transit time method for flow measurement.
Turn Down Ratio: 200:1 - Accuracy: +/- 1% – 3% of flow reading for >0.3m/s (1 ft/s).
- Flow Velocity Range: 0.1m/s – 10m/s (0.3 ft/s – 32 ft/s).
- Pipe Range: Available in 2 options. 22mm to 115mm and 125mm to 180mm OD. Note Pipe size is dependent on pipe material and internal diameter.
- Water Temp Range: 0°C – 85°C (32°F – 185°F).
Pulse Output: Pulse or Frequency.
Pulse for Volume flow and Alarms.
Frequency for flow rate.
The pulse output can be configured as a loss of signal or low flow alarm. - 4-20mA Output: O-*/º ptional 4-20mA flow proportional output
- Modbus Communication: Optional Modbus RTU slave, RS485 serial link hardware layer. Modbus connection cable is 1m.
- External Power Supply: 12V – 24V +/- 10% AC/DC at 7 watts per unit. Optional plug in 12V power supply.
- Electronics Enclosure: IP54.
- Input/Output Cable: 5m x 6 core for power in, 4-20mA and pulse out.
- Dimensions : 250mm x 48mm x 90mm (10″ x 2″ x 4″)
(electronics + guide rail).